Do you know where is the circiut breaker for those out let??????? make sure you turn if off before start any work for checking. Remember "SAFETY FIRST"
Normaly. 4 duplicate receptacle out let were wired into one singl circuit breaker.
What you need to do, open all receptacle out let that is suspected had a short, and disconnect the two black wire, it should be two black wire connected to the out let if it is in the middle or the begining of the circuit, (otherwise will be only one black wire if it is at the end of the circuit ,(parallel connection) measure both the black wire's resistance to ground,I assume that you have a DMM and understand how to use it?, this measurement will determind which end of the black wire is shorted to ground, then follow the same thing to measure all other out let, untill the faulty is found.
Normaly. 4 duplicate receptacle out let were wired into one singl circuit breaker.
What you need to do, open all receptacle out let that is suspected had a short, and disconnect the two black wire, it should be two black wire connected to the out let if it is in the middle or the begining of the circuit, (otherwise will be only one black wire if it is at the end of the circuit ,(parallel connection) measure both the black wire's resistance to ground,I assume that you have a DMM and understand how to use it?, this measurement will determind which end of the black wire is shorted to ground, then follow the same thing to measure all other out let, untill the faulty is found.